The reasons for the transformer backup protection action are as follows:
(1) short circuit on the high voltage side of the transformer.
(2) transformer low voltage bus short circuit.
(3) Due to the failure in the differential protection range, the differential protection fails.
(4) backup protection misoperation.
(5) the low voltage line fault, the outgoing line protection refused to move, causing the transformer overload trip.
The principle of treatment is:
(1) if the over-current protection action, found voltage drop, impact, arc, sound and other phenomena, should be checked outside the transformer; If the fault can be removed in time, it can be sent once, otherwise safety measures should be taken to prepare for emergency repair; If no problem is found, you can also send a trial; For transformers without differential protection, in addition to external inspection, insulation inspection should also be carried out.
(2) if the low-voltage outgoing line fails, the line protection refuses to move, you can manually knock out the fault line switch, and then send power to the transformer.
(3) If the differential protection fails due to failure within the range of differential protection, it should be handled according to the differential protection action.
(4) If it is a fault of the secondary circuit, it is a fault of operation or collision, and the personnel on duty can immediately try to transmit power.
Jinghu electrical transformer co., LTD. Is specialized in the research, design and manufacture of special transformers, reactors of professional manufacturers. Advanced process equipment, complete testing means, the enterprise after 20 years of practical experience. Transformer, dry type transformer, power transformer, transformer price, rectifier transformer, three-phase transformer, amorphous alloy transformer, voltage regulator, voltage regulator, AC regulator, voltage regulator manufacturer, voltage regulator price, charger, Inverter controlled rectifier transformer phase (single-phase transformer, three-phase transformer, six, twelve phase transformer excitation rectifier transformer, rectifier transformer, electrolytic plating rectifier transformer), transformer, corner, decompression starter autotransformer (QZB) and high voltage starting reactor (QKSQ), salt bath furnace transformer, electric resistance welding transformer, autotransformer for lighting energy-saving equipment, a high voltage testing transformer, big current generator, transformer for high frequency dielectric heating equipment, a prison high-voltage power grid equipment dedicated to prevent high voltage transformer (afraid of short circuit is not afraid of lightning), tube recovery current limiting high voltage transformer, the neon lights Impact transformers, machine tool control transformers (BK type, BKC type, JBK type), communication and electronic power transformers (EI type, C type, ED type), voltage regulator transformers, isolation transformers, all kinds of electromagnetic coils. Reactor, including into the three-phase line reactor, two phase into the line reactor, flat wave reactor, dc shunt reactor, filter reactor, flat wave reactor, input and output reactor, balanced reactor, inverter dedicated (input, output, dc) reactor, serial reactor and capacitor compensation series reactor, power filter for harmonic elimination reactor, reactor into line, current-limiting reactor, a variety of dummy load reactor, variable magnetic control reactor).