Release time:2021-03-26 14:16:34 Popularity: Source:未知
1, gas protection device operation, normal operation, heavy gas protection pressure plate throw trip position, light gas protection throw signal position. Under special circumstances, the pressure plate of heavy gas protection should be changed to signal position. The most common situation in the work is that the transformer after overhaul oil or filter oil, re-put into operation for a period of time, generally 2-3 days, until the gas or no gas bubble, then put the heavy gas protection to trip position. Operation and maintenance of tap-changer. No load voltage regulation: when changing the position of the TAP joint, turn several times in the positive and negative directions to eliminate the oxidation film and oil on the contact, pay attention to the correct position. After changing the tap position, measure whether the DC resistance is qualified or not. 2. ON-LOAD VOLTAGE REGULATION: oil samples are taken every three months for testing; electric operating mechanism is checked and kept in good condition; after 5000 changes, it is checked out. If you change the tap in the case of shutdown, the same to measure the DC resistance is eligible