What are the principles of the construction of the dry trans

Release time:2021-03-26 16:22:46 Popularity: Source:未知

In order to ensure the safety characteristics of the dry transformer, the dry transformer room should be built for the dry transformer, whether in rural or urban areas, it is necessary to build. Dry-type transformer as a more important guarantee of the safety of dry-type transformer to improve the various performance of the dry-type transformer is constantly playing a role. Dry transformer protection is to pay attention to the protection of dry transformer room, for the dry transformer room in the construction of the time is also to grasp a lot of principles, general principles include what aspects?

干式变压器室

  1, GB50054-2011 "low voltage power distribution design code" 4.3 requirements for the building: 4.3.4 distribution room cable trench, should take waterproof box drainage measures. The ground of the distribution room should be 50mm higher than the ground of this floor or a waterproof threshold should be set.

 
2, GB50053-94 "under 10 kv substation design specification" clause 4.4.2 open or half open the dry type transformer substation should be not less than 1.7 m high fixed around the fence (wall), dry type transformer profile and fence wall outside the interval should not be less than 0.8 m, in the bottom of the dry type transformer is apart from the ground should not be less than 0.3 m, the net distance between adjacent dry type transformer outside profile should not be less than 1.5 m.
 
Construction of the dry type transformer room must pay attention to the ways and methods, especially for function should be strictly carried out in accordance with the function of dry type transformer and the principle to build, so dry type transformer room to be able to enhance its role and advantage, at the time of construction of dry type transformer room careful to cut corners, shoddy the emergence of illegal behavior!
High voltage ring main unit
KBSG mine flameproof dry type transformer
KSG mine general dry type transformer

Online Message

invisibility? Click changeinvisibility?
Service
Contact

Hotline

+86-185-5293-9138

work shift

from Monday to Friday

Company phone

+86-185-5293-9138

QR code
Service